At a glance

SAFETY • A1
CURVE • bubble
POINTS • 321
GWP
2729
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.38 to 520.75
Temperature range (°F)
-150 to 170
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-45.8linear
25-3.4linear
5021.2linear
7539.4linear
10054.1linear
15077.5linear
20096linear
250111.5linear
300125linear
350136.9linear
400147.7linear
450157.5linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-402.4exact
-2012.9exact
027.9exact
2048.5exact
4075.9exact
60111.4exact
80156.3exact
100212.2exact
120280.7exact
140363.7exact

Data source & notes

PT asset ID
r422d
Original name
R-422D
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.