REFRIGERANT • PT DATA v1

R-423A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • dew
POINTS • 381
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.68 to 498.93
Temperature range (°F)
-170 to 210
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-10.3linear
2534.1linear
5060linear
7579linear
10094.4linear
150118.8linear
200138.1linear
250154.2linear
300168.2linear
350180.5linear
400191.5linear
450201.4linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-8.1exact
-20-3.2exact
04.2exact
2014.9exact
4029.9exact
6050exact
8076.4exact
100110.3exact
120152.8exact
140205.5exact

Data source & notes

PT asset ID
r423a
Original name
R-423A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.