REFRIGERANT • PT DATA v1

R-425A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • bubble
POINTS • 381
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.66 to 631.98
Temperature range (°F)
-180 to 200
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-36.7linear
256.1linear
5030.9linear
7549.2linear
10064linear
15087.5linear
200106.1linear
250121.7linear
300135.3linear
350147.4linear
400158.3linear
450168.3linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-1.2exact
-207.5exact
020.2exact
2037.8exact
4061.6exact
6092.8exact
80132.6exact
100182.5exact
120244exact
140318.7exact