REFRIGERANT • PT DATA v1

R-427A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 351
GWP
2138
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.65 to 571.46
Temperature range (°F)
-170 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-33.2linear
257.8linear
5031.6linear
7549.1linear
10063.2linear
15085.6linear
200103.3linear
250118.1linear
300130.8linear
350142.1linear
400152.2linear
450161.3linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-2.5exact
-206exact
018.7exact
2036.6exact
4061.2exact
6093.8exact
80136.1exact
100189.9exact
120257.1exact
140340.3exact

Data source & notes

PT asset ID
r427a
Original name
R-427A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.