REFRIGERANT • PT DATA v1

R-434A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 319
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.46 to 494.89
Temperature range (°F)
-158 to 160
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-49.1linear
25-7.2linear
5017.2linear
7535.3linear
10049.8linear
15072.9linear
20091.3linear
250106.7linear
300120linear
350131.8linear
400142.4linear
450152.1linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-403.9exact
-2015.3exact
031.4exact
2053.4exact
4082.7exact
60120.4exact
80168exact
100227.3exact
120299.9exact
140388.1exact

Data source & notes

PT asset ID
r434a
Original name
R-434A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.