REFRIGERANT • PT DATA v1

R-438A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 350
GWP
2264
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.63 to 563.46
Temperature range (°F)
-170 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-33.1linear
258.1linear
5032.1linear
7549.7linear
10063.9linear
15086.4linear
200104.2linear
250119.1linear
300131.9linear
350143.3linear
400153.4linear
450162.5linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-2.5exact
-205.9exact
018.5exact
2036.2exact
4060.5exact
6092.7exact
80134.4exact
100187.3exact
120253.3exact
140335exact

Data source & notes

PT asset ID
r438a
Original name
R-438A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.