REFRIGERANT • PT DATA v1

R-509A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 397
GWP
5741
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 476.83
Temperature range (°F)
-252 to 150
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-57.5linear
25-15.5linear
509.1linear
7527.3linear
10042linear
15065.3linear
20083.9linear
25099.5linear
300113linear
350124.9linear
400135.5linear
450145.2linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-408.2exact
-2021.3exact
039.7exact
2064.3exact
4096.4exact
60137.4exact
80188.6exact
100251.8exact
120328.9exact
140422.5exact

Data source & notes

PT asset ID
r509a
Original name
R-509A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.