At a glance
SAFETY • A1
CURVE • dew
POINTS • 311
GWP
7370
ODP
0.6
Curves available
Dew + Bubble
Pressure range (psig)
-14.25 to 408.9
Temperature range (°F)
-140 to 170
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | -38.6 | linear |
| 25 | 6.3 | linear |
| 50 | 32.7 | linear |
| 75 | 52.2 | linear |
| 100 | 68 | linear |
| 150 | 93.2 | linear |
| 200 | 113.2 | linear |
| 250 | 129.9 | linear |
| 300 | 144.3 | linear |
| 350 | 157 | linear |
| 400 | 168.2 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | -0.5 | exact |
| -20 | 8.1 | exact |
| 0 | 20.3 | exact |
| 20 | 36.8 | exact |
| 40 | 58.7 | exact |
| 60 | 86.8 | exact |
| 80 | 122.2 | exact |
| 100 | 166 | exact |
| 120 | 219.4 | exact |
| 140 | 284.3 | exact |
Data source & notes
PT asset ID
r115Original name
R-115
CAS
76-15-3
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.