REFRIGERANT • PT DATA v1

R-115

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 311
GWP
7370
ODP
0.6
Curves available
Dew + Bubble
Pressure range (psig)
-14.25 to 408.9
Temperature range (°F)
-140 to 170
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-38.6linear
256.3linear
5032.7linear
7552.2linear
10068linear
15093.2linear
200113.2linear
250129.9linear
300144.3linear
350157linear
400168.2linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-0.5exact
-208.1exact
020.3exact
2036.8exact
4058.7exact
6086.8exact
80122.2exact
100166exact
120219.4exact
140284.3exact

Data source & notes

PT asset ID
r115
Original name
R-115
CAS
76-15-3
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)