REFRIGERANT • PT DATA v1

R-116

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 201
GWP
12200
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-9.54 to 382.52
Temperature range (°F)
-140 to 60
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-108.6linear
25-71.2linear
50-49.3linear
75-33.1linear
100-20linear
1500.9linear
20017.4linear
25031.3linear
30043.3linear
35053.8linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-4063.7exact
-20100exact
0147.7exact
20208.7exact
40285.7exact
60382.5exact

Data source & notes

PT asset ID
r116
Original name
R-116
CAS
76-16-4
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)