REFRIGERANT • PT DATA v1

R-124

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 491
GWP
609
ODP
0.02
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 499.65
Temperature range (°F)
-240 to 250
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
010.5linear
2558.2linear
5086.1linear
75106.7linear
100123.3linear
150149.8linear
200170.8linear
250188.4linear
300203.6linear
350217.1linear
400229.2linear
450240.1linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-10.9exact
-20-7.9exact
0-3.3exact
203.6exact
4013.2exact
6026.3exact
8043.7exact
10066.2exact
12094.6exact
140129.9exact

Data source & notes

PT asset ID
r124
Original name
R-124
CAS
2837-89-0
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.