REFRIGERANT • PT DATA v1

R-13

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 371
GWP
14400
ODP
1
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 520.66
Temperature range (°F)
-290 to 80
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-114.7linear
25-77.1linear
50-55.1linear
75-38.7linear
100-25.5linear
150-4.3linear
20012.5linear
25026.7linear
30039linear
35050linear
40059.8linear
45068.7linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-4072.9exact
-20111.7exact
0161.9exact
20225.3exact
40304.1exact
60401.1exact
80520.7exact

Data source & notes

PT asset ID
r13
Original name
R-13
CAS
75-72-9
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.