REFRIGERANT • PT DATA v1
R-13
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • A1
CURVE • dew
POINTS • 371
GWP
14400
ODP
1
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 520.66
Temperature range (°F)
-290 to 80
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | -114.7 | linear |
| 25 | -77.1 | linear |
| 50 | -55.1 | linear |
| 75 | -38.7 | linear |
| 100 | -25.5 | linear |
| 150 | -4.3 | linear |
| 200 | 12.5 | linear |
| 250 | 26.7 | linear |
| 300 | 39 | linear |
| 350 | 50 | linear |
| 400 | 59.8 | linear |
| 450 | 68.7 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | 72.9 | exact |
| -20 | 111.7 | exact |
| 0 | 161.9 | exact |
| 20 | 225.3 | exact |
| 40 | 304.1 | exact |
| 60 | 401.1 | exact |
| 80 | 520.7 | exact |
Data source & notes
PT asset ID
r13Original name
R-13
CAS
75-72-9
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.