REFRIGERANT • PT DATA v1

R-142B

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A2
CURVE • dew
POINTS • 471
GWP
2310
ODP
0.07
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 525.3
Temperature range (°F)
-200 to 270
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
015.6linear
2565linear
5093.8linear
75115.2linear
100132.5linear
150160linear
200181.9linear
250200.3linear
300216.2linear
350230.3linear
400243linear
450254.5linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-11.2exact
-20-8.6exact
0-4.5exact
201.5exact
4010exact
6021.6exact
8036.9exact
10056.6exact
12081.5exact
140112.3exact

Data source & notes

PT asset ID
r142b
Original name
R-142B
CAS
75-68-3
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.