REFRIGERANT • PT DATA v1

R-152A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A2
CURVE • dew
POINTS • 411
GWP
124
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 600.72
Temperature range (°F)
-180 to 230
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-11.2linear
2533.8linear
5060linear
7579.2linear
10094.7linear
150119.4linear
200139linear
250155.3linear
300169.5linear
350182.1linear
400193.4linear
450203.7linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-7.8exact
-20-2.9exact
04.5exact
2015.2exact
4030.1exact
6050.1exact
8076.2exact
100109.5exact
120151.4exact
140203exact

Data source & notes

PT asset ID
r152a
Original name
R-152A
CAS
75-37-6
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.