REFRIGERANT • PT DATA v1

R-21

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • dew
POINTS • 441
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.5 to 718.25
Temperature range (°F)
-90 to 350
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
048linear
2599.5linear
50129.6linear
75151.8linear
100169.9linear
150198.6linear
200221.5linear
250240.8linear
300257.6linear
350272.5linear
400285.9linear
450298.2linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-13.3exact
-20-12.1exact
0-10.1exact
20-7exact
40-2.4exact
604.2exact
8013.3exact
10025.3exact
12041exact
14060.9exact

Data source & notes

PT asset ID
r21
Original name
R-21
CAS
75-43-4
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.