REFRIGERANT • PT DATA v1

R-22

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 451
GWP
1810
ODP
0.06
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 671.5
Temperature range (°F)
-250 to 200
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-41.5linear
251.2linear
5026linear
7544.3linear
10059.1linear
15082.7linear
200101.4linear
250117.1linear
300130.8linear
350142.9linear
400153.9linear
450163.9linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-400.6exact
-2010.2exact
024exact
2043.1exact
4068.6exact
60101.6exact
80143.6exact
100195.9exact
120260exact
140337.4exact

Data source & notes

PT asset ID
r22
Original name
R-22
CAS
75-45-6
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.