REFRIGERANT • PT DATA v1

R-227ea

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 401
GWP
3220
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 385.37
Temperature range (°F)
-190 to 210
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
02.6linear
2548.9linear
5075.9linear
7595.8linear
100111.9linear
150137.4linear
200157.6linear
250174.5linear
300189.1linear
350201.8linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-10exact
-20-6.4exact
0-0.9exact
207.2exact
4018.7exact
6034.2exact
8054.7exact
10081.1exact
120114.5exact
140155.9exact

Data source & notes

PT asset ID
r227ea
Original name
R-227ea
CAS
431-89-0
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.