REFRIGERANT • PT DATA v1
R-227ea
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • A1
CURVE • dew
POINTS • 401
GWP
3220
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 385.37
Temperature range (°F)
-190 to 210
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | 2.6 | linear |
| 25 | 48.9 | linear |
| 50 | 75.9 | linear |
| 75 | 95.8 | linear |
| 100 | 111.9 | linear |
| 150 | 137.4 | linear |
| 200 | 157.6 | linear |
| 250 | 174.5 | linear |
| 300 | 189.1 | linear |
| 350 | 201.8 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | -10 | exact |
| -20 | -6.4 | exact |
| 0 | -0.9 | exact |
| 20 | 7.2 | exact |
| 40 | 18.7 | exact |
| 60 | 34.2 | exact |
| 80 | 54.7 | exact |
| 100 | 81.1 | exact |
| 120 | 114.5 | exact |
| 140 | 155.9 | exact |
Data source & notes
PT asset ID
r227eaOriginal name
R-227ea
CAS
431-89-0
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version