REFRIGERANT • PT DATA v1

R-236ea

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • dew
POINTS • 301
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-11.97 to 461.25
Temperature range (°F)
-20 to 280
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
043.2linear
2592.2linear
50120.6linear
75141.7linear
100158.6linear
150185.6linear
200207linear
250224.9linear
300240.3linear
350254.1linear
400266.4linear
450277.6linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-20-12exact
0-9.8exact
20-6.3exact
40-1exact
606.5exact
8016.9exact
10031exact
12049.3exact
14072.8exact

Data source & notes

PT asset ID
r236ea
Original name
R-236ea
CAS
431-63-0
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.