REFRIGERANT • PT DATA v1

R-236fa

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 381
GWP
9810
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.66 to 416.24
Temperature range (°F)
-130 to 250
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
029.4linear
2577.3linear
50105.1linear
75125.7linear
100142.3linear
150168.7linear
200189.5linear
250206.8linear
300221.7linear
350234.8linear
400246.5linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-12.6exact
-20-10.7exact
0-7.7exact
20-2.9exact
404exact
6013.8exact
8027.1exact
10044.7exact
12067.4exact
14096.2exact

Data source & notes

PT asset ID
r236fa
Original name
R-236fa
CAS
690-39-1
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.