REFRIGERANT • PT DATA v1

R-290

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A3
CURVE • dew
POINTS • 501
GWP
3
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 565.1
Temperature range (°F)
-300 to 200
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-43.8linear
251.7linear
5028.4linear
7548.2linear
10064.2linear
15089.8linear
200110.1linear
250127.3linear
300142.2linear
350155.4linear
400167.3linear
450178.2linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-401.4exact
-2010.7exact
023.7exact
2041.1exact
4063.9exact
6093exact
80129.3exact
100173.9exact
120227.8exact
140292.3exact

Data source & notes

PT asset ID
r290
Original name
R-290
CAS
74-98-6
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.