REFRIGERANT • PT DATA v1

R-32

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A2
CURVE • dew
POINTS • 381
GWP
675
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 798.88
Temperature range (°F)
-210 to 170
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-61linear
25-22linear
500.6linear
7517.1linear
10030.4linear
15051.6linear
20068.2linear
25082.2linear
30094.3linear
350105.1linear
400114.7linear
450123.5linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-4011exact
-2026.8exact
049.3exact
2080exact
40121exact
60174exact
80241.5exact
100325.7exact
120429.3exact
140555.8exact

Data source & notes

PT asset ID
r32
Original name
R-32
CAS
27672
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.