REFRIGERANT • PT DATA v1
R-365MFC
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • A2
CURVE • dew
POINTS • 381
GWP
890
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-28.88 to 407.79
Temperature range (°F)
-20 to 360
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | 141.8 | linear |
| 25 | 180.3 | linear |
| 50 | 206.8 | linear |
| 75 | 227.6 | linear |
| 100 | 244.9 | linear |
| 150 | 273 | linear |
| 200 | 295.5 | linear |
| 250 | 314.5 | linear |
| 300 | 330.9 | linear |
| 350 | 345.3 | linear |
| 400 | 358.1 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -20 | -28.9 | exact |
| 0 | -28.4 | exact |
| 20 | -27.5 | exact |
| 40 | -26.1 | exact |
| 60 | -23.9 | exact |
| 80 | -20.6 | exact |
| 100 | -15.9 | exact |
| 120 | -9.5 | exact |
| 140 | -0.9 | exact |
Data source & notes
PT asset ID
r365mfcOriginal name
R-365MFC
CAS
406-58-6
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.