REFRIGERANT • PT DATA v1

R-401B

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 421
GWP
1288
ODP
0.04
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 655.38
Temperature range (°F)
-200 to 220
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-30.2linear
2514.1linear
5039.9linear
7559linear
10074.4linear
15099linear
200118.6linear
250135linear
300149.3linear
350162linear
400173.5linear
450184linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-3.3exact
-204.1exact
014.9exact
2029.9exact
4050.1exact
6076.5exact
80110.2exact
100152.3exact
120204exact
140266.7exact

Data source & notes

PT asset ID
r401b
Original name
R-401B
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.