REFRIGERANT • PT DATA v1

R-401C

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 431
GWP
933
ODP
0.03
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 592.91
Temperature range (°F)
-200 to 230
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-9linear
2536linear
5062.1linear
7581.4linear
10097linear
150121.7linear
200141.3linear
250157.7linear
300171.8linear
350184.4linear
400195.6linear
450205.8linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-8.3exact
-20-3.6exact
03.5exact
2013.9exact
4028.2exact
6047.6exact
8072.9exact
100105.4exact
120146.1exact
140196.4exact

Data source & notes

PT asset ID
r401c
Original name
R-401C
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.