REFRIGERANT • PT DATA v1

R-403A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 451
GWP
3124
ODP
0.04
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 608.31
Temperature range (°F)
-270 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-53.9linear
25-10.9linear
5014.2linear
7532.6linear
10047.6linear
15071.4linear
20090.3linear
250106.1linear
300119.9linear
350132.1linear
400143.1linear
450153.1linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-406.1exact
-2018.1exact
034.7exact
2057.2exact
4086.7exact
60124.4exact
80171.6exact
100229.8exact
120300.5exact
140385.6exact

Data source & notes

PT asset ID
r403a
Original name
R-403A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.