REFRIGERANT • PT DATA v1

R-407E

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 371
GWP
1600
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.67 to 648.94
Temperature range (°F)
-180 to 190
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-31.9linear
259linear
5032.7linear
7550.2linear
10064.2linear
15086.4linear
200104linear
250118.6linear
300131.3linear
350142.5linear
400152.5linear
450161.5linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-3exact
-205.4exact
017.7exact
2035.4exact
4059.7exact
6092exact
80134.2exact
100187.8exact
120255.1exact
140338.5exact

Data source & notes

PT asset ID
r407e
Original name
R-407E
CAS
75-10-5/354-33-16/811-97-2
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)