REFRIGERANT • PT DATA v1

R-409A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 436
GWP
1585
ODP
0.05
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 591.99
Temperature range (°F)
-228 to 220
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-14.7linear
2529.4linear
5055.1linear
7574linear
10089.3linear
150113.6linear
200132.8linear
250148.9linear
300162.8linear
350175.1linear
400186.2linear
450196.2linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-7.3exact
-20-1.8exact
06.3exact
2018exact
4034.2exact
6055.9exact
8084.2exact
100120.3exact
120165.6exact
140221.3exact

Data source & notes

PT asset ID
r409a
Original name
R-409A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.