REFRIGERANT • PT DATA v1

R-409B

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 438
GWP
1620
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 628.25
Temperature range (°F)
-229 to 220
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-18.2linear
2525.6linear
5051linear
7569.8linear
10085linear
150109.1linear
200128.1linear
250144.1linear
300157.9linear
350170.2linear
400181.1linear
450191.1linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-6.5exact
-20-0.7exact
08.1exact
2020.7exact
4038exact
6061.2exact
8091.3exact
100129.6exact
120177.5exact
140236.4exact

Data source & notes

PT asset ID
r409b
Original name
R-409B
CAS
75-45-6 / 75-45-6 / 2837-89-0
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.