REFRIGERANT • PT DATA v1

R-410B

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 341
GWP
2229
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.65 to 608.36
Temperature range (°F)
-190 to 150
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-60.2linear
25-21linear
501.7linear
7518.4linear
10031.9linear
15053.2linear
20070.2linear
25084.3linear
30096.6linear
350107.5linear
400117.2linear
450126.1linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-4010.5exact
-2025.9exact
047.8exact
2077.7exact
40117.4exact
60168.8exact
80233.9exact
100315.1exact
120415exact
140537.3exact

Data source & notes

PT asset ID
r410b
Original name
R-410B
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.