At a glance

SAFETY • A2
CURVE • dew
POINTS • 411
GWP
1705
ODP
0.05
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 666.94
Temperature range (°F)
-210 to 200
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-40linear
252.4linear
5027.1linear
7545.4linear
10060.1linear
15083.6linear
200102.3linear
250118linear
300131.7linear
350143.8linear
400154.7linear
450164.7linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-400exact
-209.5exact
023.1exact
2041.9exact
4067exact
6099.7exact
80141.4exact
100193.2exact
120256.8exact
140333.8exact

Data source & notes

PT asset ID
r411b
Original name
R-411B
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.