REFRIGERANT • PT DATA v1

R-417A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 341
GWP
2346
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.63 to 507.8
Temperature range (°F)
-160 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-29.4linear
2512.5linear
5036.8linear
7554.8linear
10069.3linear
15092.3linear
200110.5linear
250125.7linear
300138.9linear
350150.5linear
400160.9linear
450170.3linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-3.7exact
-204exact
015.5exact
2031.7exact
4054exact
6083.5exact
80121.7exact
100170exact
120230.3exact
140304.4exact

Data source & notes

PT asset ID
r417a
Original name
R-417A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.