REFRIGERANT • PT DATA v1

R-421A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 328
GWP
2600
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.55 to 543.24
Temperature range (°F)
-148 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-31.7linear
259.7linear
5033.7linear
7551.5linear
10065.8linear
15088.5linear
200106.4linear
250121.4linear
300134.4linear
350145.9linear
400156.1linear
450165.4linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-3exact
-205.2exact
017.3exact
2034.6exact
4058.1exact
6089.4exact
80129.8exact
100181exact
120244.9exact
140323.6exact

Data source & notes

PT asset ID
r421a
Original name
R-421A
CAS
354-33-6 / 811-97-2
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.