REFRIGERANT • PT DATA v1

R-421B

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 309
GWP
3200
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.44 to 511.19
Temperature range (°F)
-148 to 160
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-44.4linear
25-3.8linear
5019.8linear
7537.3linear
10051.4linear
15073.8linear
20091.6linear
250106.5linear
300119.3linear
350130.7linear
400140.9linear
450150linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-401.9exact
-2012.7exact
028.4exact
2050.2exact
4079.4exact
60117.6exact
80166.3exact
100227.3exact
120302.8exact
140395.5exact

Data source & notes

PT asset ID
r421b
Original name
R-421B
CAS
354-33-6 / 811-97-2
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)