REFRIGERANT • PT DATA v1
R-422C
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • A1
CURVE • dew
POINTS • 318
GWP
3100
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.54 to 508.06
Temperature range (°F)
-157 to 160
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | -45.1 | linear |
| 25 | -4.4 | linear |
| 50 | 19.3 | linear |
| 75 | 36.9 | linear |
| 100 | 51.1 | linear |
| 150 | 73.7 | linear |
| 200 | 91.6 | linear |
| 250 | 106.6 | linear |
| 300 | 119.5 | linear |
| 350 | 131 | linear |
| 400 | 141.2 | linear |
| 450 | 150.5 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | 2.2 | exact |
| -20 | 13.2 | exact |
| 0 | 29 | exact |
| 20 | 50.8 | exact |
| 40 | 80.1 | exact |
| 60 | 118.1 | exact |
| 80 | 166.6 | exact |
| 100 | 227.2 | exact |
| 120 | 301.9 | exact |
| 140 | 393.6 | exact |
Data source & notes
PT asset ID
r422cOriginal name
R-422C
CAS
354-33-6 / 811-97-2 / 75-28-5
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.