REFRIGERANT • PT DATA v1
R-424A
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • —
CURVE • dew
POINTS • 331
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.57 to 516.84
Temperature range (°F)
-150 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | -29.8 | linear |
| 25 | 11.9 | linear |
| 50 | 36.2 | linear |
| 75 | 54.1 | linear |
| 100 | 68.5 | linear |
| 150 | 91.4 | linear |
| 200 | 109.6 | linear |
| 250 | 124.7 | linear |
| 300 | 137.8 | linear |
| 350 | 149.4 | linear |
| 400 | 159.7 | linear |
| 450 | 169 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | -3.6 | exact |
| -20 | 4.3 | exact |
| 0 | 15.9 | exact |
| 20 | 32.3 | exact |
| 40 | 54.8 | exact |
| 60 | 84.7 | exact |
| 80 | 123.4 | exact |
| 100 | 172.4 | exact |
| 120 | 233.6 | exact |
| 140 | 308.9 | exact |
Data source & notes