REFRIGERANT • PT DATA v1

R-430A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • dew
POINTS • 431
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 549.55
Temperature range (°F)
-210 to 220
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-17.4linear
2528.1linear
5054.6linear
7574.3linear
10090.1linear
150115.4linear
200135.4linear
250152.2linear
300166.7linear
350179.6linear
400191.2linear
450201.7linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-6.6exact
-20-0.9exact
07.4exact
2019.1exact
4035.1exact
6056.2exact
8083.5exact
100118exact
120160.7exact
140213exact

Data source & notes

PT asset ID
r430a
Original name
R-430A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.