REFRIGERANT • PT DATA v1
R-431A
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • A3
CURVE • dew
POINTS • 431
GWP
38.3
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 595.94
Temperature range (°F)
-243 to 197
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | -45.8 | linear |
| 25 | -1.2 | linear |
| 50 | 25 | linear |
| 75 | 44.3 | linear |
| 100 | 60 | linear |
| 150 | 85 | linear |
| 200 | 104.8 | linear |
| 250 | 121.5 | linear |
| 300 | 136 | linear |
| 350 | 148.9 | linear |
| 400 | 160.5 | linear |
| 450 | 171 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | 2.2 | exact |
| -20 | 12.1 | exact |
| 0 | 25.9 | exact |
| 20 | 44.5 | exact |
| 40 | 68.9 | exact |
| 60 | 100 | exact |
| 80 | 139 | exact |
| 100 | 186.9 | exact |
| 120 | 245.1 | exact |
| 140 | 314.8 | exact |
Data source & notes
PT asset ID
r431aOriginal name
R-431A
CAS
—
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.