REFRIGERANT • PT DATA v1

R-443A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • bubble
POINTS • 449
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 608.22
Temperature range (°F)
-259 to 200
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-49.4linear
25-4.4linear
5021.9linear
7541.5linear
10057.4linear
15082.7linear
200102.9linear
250119.9linear
300134.7linear
350147.9linear
400159.7linear
450170.6linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-403.7exact
-2014.2exact
028.6exact
2047.8exact
4072.9exact
60104.6exact
80144.1exact
100192.3exact
120250.4exact
140319.5exact

Data source & notes

PT asset ID
r443a
Original name
R-443A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.