REFRIGERANT • PT DATA v1

R-444A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • dew
POINTS • 391
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.68 to 554.24
Temperature range (°F)
-180 to 210
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-12.7linear
2531.1linear
5056.5linear
7575.2linear
10090.2linear
150114linear
200132.7linear
250148.4linear
300161.8linear
350173.6linear
400184.1linear
450193.5linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-7.7exact
-20-2.5exact
05.3exact
2016.8exact
4032.7exact
6054.2exact
8082.5exact
100118.9exact
120164.9exact
140222.2exact

Data source & notes

PT asset ID
r444a
Original name
R-444A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.