REFRIGERANT • PT DATA v1

R-507A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 301
GWP
3985
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.31 to 467.42
Temperature range (°F)
-150 to 150
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-52.1linear
25-10.6linear
5013.6linear
7531.5linear
10045.9linear
15068.8linear
20087linear
250102.2linear
300115.4linear
350127linear
400137.5linear
450146.9linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-405.4exact
-2017.6exact
034.8exact
2058.3exact
4089.2exact
60129.2exact
80179.6exact
100242.3exact
120319.2exact
140413exact

Data source & notes

PT asset ID
r507a
Original name
R-507A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.