REFRIGERANT • PT DATA v1

R-508A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 267
GWP
13214
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.47 to 512.37
Temperature range (°F)
-216 to 50
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-125.7linear
25-91linear
50-70.8linear
75-55.8linear
100-43.7linear
150-24.5linear
200-9.3linear
2503.5linear
30014.6linear
35024.4linear
40033.1linear
45041.1linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40108.7exact
-20163.8exact
0235.5exact
20327exact
40442.8exact

Data source & notes

PT asset ID
r508a
Original name
R-508A
CAS
75-46-7, 76-16-4
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.