REFRIGERANT • PT DATA v1

R-601

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY •
CURVE • dew
POINTS • 581
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 450.54
Temperature range (°F)
-200 to 380
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
096.9linear
25155.7linear
50190linear
75215.4linear
100236linear
150268.7linear
200294.6linear
250316.4linear
300335.2linear
350351.7linear
400366.5linear
450379.9linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-14.3exact
-20-13.9exact
0-13.2exact
20-12.1exact
40-10.4exact
60-7.8exact
80-4.2exact
1000.9exact
1207.6exact
14016.4exact

Data source & notes

PT asset ID
r601
Original name
R-601
CAS
109-66-0
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.