REFRIGERANT • PT DATA v1

R-717

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • B2
CURVE • dew
POINTS • 371
GWP
0
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-13.46 to 1629.1
Temperature range (°F)
-100 to 270
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-28linear
2511.3linear
5033.8linear
7550.3linear
10063.5linear
15084.3linear
200100.8linear
250114.6linear
300126.5linear
350137.1linear
400146.7linear
450155.4linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-4.3exact
-203.6exact
015.7exact
2033.5exact
4058.6exact
6092.9exact
80138.4exact
100197.3exact
120271.9exact
140364.7exact

Data source & notes

PT asset ID
r717
Original name
R-717
CAS
7664-41-7
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.