REFRIGERANT • PT DATA v1

R-407A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 359
GWP
2107
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.67 to 625.59
Temperature range (°F)
-179 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-37.5linear
252.9linear
5026.3linear
7543.5linear
10057.4linear
15079.4linear
20096.8linear
250111.3linear
300123.8linear
350134.9linear
400144.8linear
450153.8linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-1exact
-208.5exact
022.5exact
2042.3exact
4069.4exact
60105.2exact
80151.6exact
100210.4exact
120284exact
140375.1exact

Data source & notes

PT asset ID
r407a
Original name
R-407A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.