REFRIGERANT • PT DATA v1

R-407A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 359
GWP
2107
ODP
0
Curves available
Dew + Bubble
Pressure range (psig)
-14.64 to 640.04
Temperature range (°F)
-179 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-49linear
25-7.9linear
5016linear
7533.6linear
10047.9linear
15070.5linear
20088.4linear
250103.5linear
300116.6linear
350128.3linear
400138.8linear
450148.4linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-403.9exact
-2015.6exact
032.2exact
2055.1exact
4085.6exact
60125.2exact
80175.3exact
100237.6exact
120314exact
140406.2exact

Data source & notes

PT asset ID
r407a
Original name
R-407A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.