REFRIGERANT • PT DATA v1

R-407F

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 370
GWP
1824
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.68 to 662.71
Temperature range (°F)
-189 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-39.4linear
250.7linear
5023.9linear
7541linear
10054.8linear
15076.6linear
20093.8linear
250108.2linear
300120.6linear
350131.6linear
400141.4linear
450150.3linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-0.2exact
-209.7exact
024.4exact
2045.1exact
4073.4exact
60110.8exact
80159.2exact
100220.6exact
120297.4exact
140392.4exact

Data source & notes

PT asset ID
r407f
Original name
R-407F
CAS
75-10-5/354-33-16/811-97-2
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.