REFRIGERANT • PT DATA v1

R-407F

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 370
GWP
1824
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.66 to 672.33
Temperature range (°F)
-189 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-50.9linear
25-10.1linear
5013.6linear
7531linear
10045.1linear
15067.5linear
20085.3linear
250100.2linear
300113.2linear
350124.7linear
400135.1linear
450144.6linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-404.9exact
-2017.1exact
034.5exact
2058.5exact
4090.3exact
60131.7exact
80184.1exact
100249.3exact
120329exact
140425.4exact

Data source & notes

PT asset ID
r407f
Original name
R-407F
CAS
75-10-5/354-33-16/811-97-2
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.