REFRIGERANT • PT DATA v1
R-407F
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • A1
CURVE • bubble
POINTS • 370
GWP
1824
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.66 to 672.33
Temperature range (°F)
-189 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | -50.9 | linear |
| 25 | -10.1 | linear |
| 50 | 13.6 | linear |
| 75 | 31 | linear |
| 100 | 45.1 | linear |
| 150 | 67.5 | linear |
| 200 | 85.3 | linear |
| 250 | 100.2 | linear |
| 300 | 113.2 | linear |
| 350 | 124.7 | linear |
| 400 | 135.1 | linear |
| 450 | 144.6 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | 4.9 | exact |
| -20 | 17.1 | exact |
| 0 | 34.5 | exact |
| 20 | 58.5 | exact |
| 40 | 90.3 | exact |
| 60 | 131.7 | exact |
| 80 | 184.1 | exact |
| 100 | 249.3 | exact |
| 120 | 329 | exact |
| 140 | 425.4 | exact |
Data source & notes
PT asset ID
r407fOriginal name
R-407F
CAS
75-10-5/354-33-16/811-97-2
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version