REFRIGERANT • PT DATA v1

R-408A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 381
GWP
3152
ODP
0.03
Curves available
Dew + Bubble
Pressure range (psig)
-14.68 to 596.18
Temperature range (°F)
-200 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-47.4linear
25-5.2linear
5019.5linear
7537.6linear
10052.3linear
15075.7linear
20094.2linear
250109.8linear
300123.3linear
350135.2linear
400146linear
450155.8linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-403.1exact
-2014exact
029.5exact
2050.7exact
4078.7exact
60115exact
80160.8exact
100217.6exact
120287.3exact
140371.5exact

Data source & notes

PT asset ID
r408a
Original name
R-408A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.