REFRIGERANT • PT DATA v1

R-408A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • bubble
POINTS • 381
GWP
3152
ODP
0.03
Curves available
Dew + Bubble
Pressure range (psig)
-14.68 to 597.07
Temperature range (°F)
-200 to 180
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-48.2linear
25-5.9linear
5018.8linear
7537linear
10051.7linear
15075.1linear
20093.7linear
250109.3linear
300122.8linear
350134.8linear
400145.6linear
450155.4linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-403.5exact
-2014.5exact
030.1exact
2051.5exact
4079.7exact
60116.1exact
80162.1exact
100219.2exact
120288.9exact
140373.3exact

Data source & notes

PT asset ID
r408a
Original name
R-408A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.