REFRIGERANT • PT DATA v1

R-415B

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A2
CURVE • dew
POINTS • 407
GWP
546
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.68 to 641.68
Temperature range (°F)
-176 to 230
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-14.5linear
2530linear
5055.8linear
7574.9linear
10090.2linear
150114.6linear
200133.9linear
250150.1linear
300164.2linear
350176.6linear
400187.8linear
450198linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-7.2exact
-20-1.9exact
06.1exact
2017.7exact
4033.6exact
6055exact
8082.8exact
100118.4exact
120162.9exact
140217.8exact

Data source & notes

PT asset ID
r415b
Original name
R-415B
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)