REFRIGERANT • PT DATA v1

R-415B

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A2
CURVE • bubble
POINTS • 407
GWP
546
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.68 to 643.6
Temperature range (°F)
-176 to 230
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-16.5linear
2528.2linear
5054.1linear
7573.2linear
10088.6linear
150113.2linear
200132.6linear
250148.9linear
300163linear
350175.6linear
400186.9linear
450197.1linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-6.8exact
-20-1.2exact
07.1exact
2018.9exact
4035.3exact
6057.1exact
8085.4exact
100121.5exact
120166.5exact
140221.7exact

Data source & notes

PT asset ID
r415b
Original name
R-415B
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.